FAMCL-01

FAMCL-01

FAMCL-01  Remote I/O FAM Series CC-Link MASTER MODULE

(Yokogawa Electric PLC use)
详情

MODEL: FAMCL-01

ORDERING INFORMATION

• Code number: FAMCL-01

RELATED PRODUCTS

• Yokogawa Electric PLC: FA-M3V
  Recommended CPU module: F3SP71-4S, F3SP76-7S, 
  F3SP22
• Configurator software (model: FAMCLCFG)
Configurator software downloadable at our web site. In order to use FAMCLCFG, YOKOGAWA Electric Corporation 'WideField3' (R.3.02 or later) is required. FAMCL-01 and a PC are connected through the CPU unit of FA-M3V.

PACKAGE INCLUDES...

• Terminating resistor 110Ω (0.5W): 2 pcs.

GENERAL SPECIFICATIONS

Connection
  CC-Link
: Separable tension clamp terminal
  Cable connector : TFMC1,5 / 5–STF–3,5
  (Phoenix Contact) (included in the package)
Applicable wire size : 0.2 − 1.5 mm 2 ; stripped length 10 mm
Recommended solderless terminal
• AI0,25−10YE 0.25 mm 2  (Phoenix Contact)
• AI0,34−10TQ 0.34 mm 2  (Phoenix Contact)
• AI0,5−10WH 0.5 mm 2  (Phoenix Contact)
• AI0,75−10GY 0.75 mm 2  (Phoenix Contact)
• A1−10 1.0 mm 2  (Phoenix Contact)
• A1,5−10 1.5 mm 2  (Phoenix Contact)
Internal bus : Via the Installation Base
Internal   Power : Via the Installation Base
Max. installable module : 2
Installable unit : Main unit and sub unit
Isolation : CC-Link or FG to internal bus or internal power
Status indicator LEDs :
• RDY, RUN, LRUN, SD, RD: Green LED
• ERR, LERR: Red LED

CC-Link COMMUNICATION

CC-Link : Ver. 1.10/2.00
Master function : Master station (local station, standby master station not supported)
Station address : 00 (Use with '00'. Works as '00' even set to other than '00'.)
Supported slave station :
  Remote I/O station
  Remote device station (Ver. 1.10)
  Remote device station (Ver. 2.00)
  Intelligent device station, local station not supported
Max. number of units connected :
  64 (Remote I/O station)
  42 (Remote device station)
Max. number of link points :
  RX: 8192 (Data unit: bit)
  RY: 8192 (Data unit: bit)
  RWr: 2048 (Data unit: word)
  Rww: 2048 (Data unit: word)
Protocol : CC-Link Ver. 1.10 conformed
Network topology : Multi-drop
Max. overall cable extension length :
  100 m (10 Mbps), 160 m (5 Mbps),
  400 m (2.5 Mbps), 900 m (625 kbps),
  1200 m (156 kbps)
Transmission media : CC-Link Ver. 1.10 compatible cable
Operational station : Master station
Operational mode : On-line mode
Communication mode : Cyclic transmission 
Baud rate : 156 kbps, 625 kbps, 2.5 Mbps, 5 Mbps, 10 Mbps, set with rotary switch
Slave station settings : With configurator software (model: FAMCLCFG)

INSTALLATION

Current consumption : 600 mA @ 5V DC
Operating temperature : 0 to 55°C (32 to 131°F)
Operating humidity : 10 to 90 %RH (non-condensing)
Atmosphere : No corrosive gas or heavy dust
Mounting : Installation Base Module (model: F3BUxx-0N or F3BU05-0D)
Weight : 150 g (0.33 lb)

PERFORMANCE

Insulation resistance : ≥ 100 MΩ with 500 V DC
Dielectric strength : 1500 V AC @ 1 minute (CC-Link or FG to internal bus or internal power)

STANDARDS & APPROVALS

EU conformity :
EMC Directive 
  EMI EN 61000-6-4
  EMS EN 61000-6-2
RoHS Directive